Surge protection for two signal wires with common reference potential, e.g., Digital IN/OUT. Can be used in safety-related circuits up to SIL 3.
Surge protection for two signal wires with common reference potential, e.g., Digital IN/OUT. Can be used in safety-related circuits up to SIL 3.
| Direction of action | Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground |
| Maximum continuous voltage UC | 30 V DC |
| 21 V AC | |
| Rated current | 600 mA (40 °C) |
| Operating effective current IC at UC | ≤ 5 µA |
| Residual current IPE | ≤ 10 µA |
| Nominal discharge current In (8/20) µs (line-ground) | 5 kA |
| Pulse discharge current Iimp (10/350) µs (line-earth) | 0.5 kA |
| Total discharge current Itotal (8/20) µs | 10 kA |
| Voltage protection level Up (line-earth) | ≤ 140 V (C1 - 1 kV / 500 A) |
| ≤ 130 V (C2 - 10 kV / 5 kA) | |
| ≤ 45 V (C3 - 25 A) | |
| ≤ 50 V (C3 - 100 A) | |
| Voltage protection level Up static (line-earth) | ≤ 55 V (C1 - 1 kV / 500 A) |
| ≤ 80 V (C2 - 10 kV / 5 kA) | |
| Response time tA (line-earth) | ≤ 1 ns |
| Input attenuation aE, asym. | typ. 0.3 dB (≤ 270 kHz/150 Ω) |
| typ. 0.3 dB (≤ 407 kHz / 100 Ω) | |
| Cut-off frequency fg (3 dB), asym. (PE) in 100 Ω system | typ. 1280 kHz |
| Cut-off frequency fg (3 dB), asym. (PE) in 150 Ω system | typ. 960 kHz |
| Capacity (Core-Earth) | typ. 2.2 nF |
| Resistance per path | 1.65 Ω ±20 % |
| Surge protection fault message | none |
| Max. required back-up fuse | 630 mA (FF) |
| Impulse durability (line-earth) | C1 - 1 kV / 500 A |
| C2 - 10 kV / 5 kA | |
| C3 - 100 A | |
| D1 - 500 A | |
| Pulse reset time (line-earth) | ≤ 300 ms |
| Additional technical data | |
| Max. total discharge current I total max (8/20) µs | 20 kA (1x) |