EEM-MA371 - Measuring device
Loading...
Yêu cầu báo giá
Loading...
Yêu cầu báo giá

EEM-MA371 - Measuring device

Product Code:
2908307
Product Price:
Contact

Multi-functional energy measuring device with direct Rogowski connection and integrated Modbus/TCP interface for measuring electrical parameters in low-voltage installations up to 690 V. (phoenixcontact.com/empro-help)

Multi-functional energy measuring device with direct Rogowski connection and integrated Modbus/TCP interface for measuring electrical parameters in low-voltage installations up to 690 V. (phoenixcontact.com/empro-help)

Maximum power dissipation for nominal condition10 VA
Mains type3-phase (3 or 4-conductor), 2-phase (2-conductor), and single-phase (1-conductor)
Electrical isolation
Test voltage4 kV AC (50 Hz, 60 s)
Pollution degree2
InsulationReinforced insulation
Electrical isolation Housing against all potentials IEC 61010-1
Standards/regulationsIEC 61010-1
Overvoltage categoryIII (300 V AC)
II (600 V AC)
InsulationReinforced insulation
Electrical isolation Supply against all other potentials IEC 61010-1
Standards/regulationsIEC 61010-1
Overvoltage categoryIII (300 V AC)
II (600 V AC)
InsulationReinforced insulation
Electrical isolation Voltage measurement input against all other potentials IEC 61010-2-030
Standards/regulationsIEC 61010-2-030
Measuring categoryIII (300 V AC)
II (600 V AC)
InsulationReinforced insulation
Electrical isolation Digital I/Os
InsulationFunctional insulation
Electrical isolation Communication interface
InsulationFunctional insulation
Supply
Supply voltage range100 V AC ... 230 V AC (±20 %)
150 V DC ... 250 V DC (±20 %)
Power consumption≤ 4 W
Nominal frequency50 Hz ... 60 Hz (AC sine)

General
Measuring principleTrue r.m.s. value measurement
Measured valueAC sine (50 Hz/60 Hz)
Acquisition of harmonicsup to 63rd harmonic
Description of the inputDigital input in accordance with IEC/EN 61131-2 (type 3)
Number1
Voltage input signal24 V DC
0 V DC ... 30 V DC
Current input signal2 mA ... 15 mA
Protection250 mA (fast-blow)
Protective circuitProtection against incorrect DC connection (max. 30 V)
Measurement: Voltage
Input nameVoltage measuring input V1, V2, V3
Input voltage range direct35 V AC ... 690 V AC (Phase/Phase)
20 V AC ... 400 V AC (Phase/neutral conductor)
Input voltage range via external transformers60 V AC ... 2000000 V AC (primary)
60 V AC ... 400 V AC (secondary)
Surge voltage capacity760 V AC (Phase/Phase)
Precision0.2 %
Power consumption< 2 VA
Measurement: Current
Input nameCurrent measurement RC1, RC2, RC3
Input current≤ 400 A (Measurement level 1)
≤ 4000 A (Measurement level 2)
Input measuring range voltage500 µV ... 400 mV (1000 A)
Response threshold from measuring range nominal value5 A
Operate threshold500 µV (5 A)
Precision0.5 %
Measurement: Power
Precision1 %
Real energy (IEC 62053-21)Class 1
Reactive power (IEC 62053-23)Class 2

Output descriptionDigital output in accordance with IEC/EN 61131-2 (type 3)
Number1
Current output signal≤ 100 mA
Voltage output signal24 V DC
Protection250 mA (fast-blow)
Protective circuitProtection against incorrect DC connection (max. 30 V)
Xem thêm
  • Chia sẻ qua viber bài: EEM-MA371 - Measuring device
  • Chia sẻ qua reddit bài:EEM-MA371 - Measuring device

Bài viết gần đây

Loading...

Danh mục Sản phẩm

Loading...

Thư viện ảnh

Loading...

Sản Phẩm liên quan

Loading...
Loading...
Loading...
zalo:0982200415